Features

Simplified electrical connections

-  A single power supply point without neutral

-  Main disconnect switch with high trip capacity

- Transformer for safe 24 V control circuit supply included

Fast commissioning

- Systematic factory operation test before shipment

-  Quick-test function for step-by-step verification of the instruments, electrical components and motors

Quiet operation

Compressors

-  Low-noise scroll compressors with low vibration level

- The compressor assembly is installed on an independent chassis and supported by anti-vibration mountings

-  Dynamic suction and discharge piping support, minimizing vibration transmission (Carrier patent)

運行寧靜

*新一代全封閉渦旋壓縮機運轉光滑平穩、振動小,排氣側雙層浮動密封進一步降低雜訊。

*獨具匠心的壓縮機彈性減振底座設計有效阻斷壓縮機振動傳遞。

*新型低雜訊軸流風扇翼型經優化設計,氣流通過葉片表面更平順,獨特的剛性支撐結構消除了振動和雜訊,通過機組框架放大的現象,機組啟動和運轉更安靜。

*雙速風機電機在部分負荷和室外空氣溫度較低時自動切換到低速,也可根據時間表程式設定夜間風機低速運轉,給您帶來更多寧靜。

Condenser section

-  Vertical condenser coils

-  Protection grilles on anti-vibration mountings to protect the heat exchanger against possible shocks.

-  Low-noise latest-generation Flying Bird IV fans (Carrier patent) , made of a composite material are now even quieter and do not generate intrusive low-frequency noise

-  Rigid fan installation for reduced start-up noise (Carrier patent)

Economical operation

Increased energy efficiency at part load

-  The refrigerant circuit includes several compressors connected in parallel. At part load, around 99% of the operating time, only the compressors that are absolutely necessary operate. At these conditions the compressors operating are more energy efficient, as they use the total condenser and evaporator capacity.

-  The electronic expansion device (EXV) allows operation at a lower condensing pressure (EER, COP and ESEER optimization).

-  Dynamic superheat management for better utilization of the evaporator heat exchange surface.

-  Defrost cycle optimization (30RQ)

-  Very efficient

- gives an increased energy efficiency ratio

Leak-tight refrigerant circuit

-  Brazed refrigerant connections for increased leaktightness

-  Reduction of leaks due to reduced vibration levels and elimination of capillary tubes (TXVs)

-  Verification of pressure transducers and temperature sensors without transferring refrigerant charge

 
  1. 無洩漏製冷回路設計:所有制冷管路及部件均採用焊接聯接,選用電子式
  2. 溫度計和電子式壓力感測器,從根本上消除各種潛在洩露可能。

Superior reliability

 State-of-the-art concept

-  Cooperation with specialist laboratories and use of limit simulation tools (finite element calculations) for the design of the critical components, e.g. motor supports, suction/discharge piping etc.

 

Exceptional endurance tests

-  Corrosion resistance tests in salt mist in the laboratory

-  Accelerated ageing test on components that are submitted to continuous operation: compressor piping, fan supports

-  Transport simulation test in the laboratory on a

vibrating table.

  1.  苛刻的耐久性測試、鹽霧耐腐蝕性試驗、加速疲勞試驗、類比運輸試驗等
  2. 確保了冷水機組極高的可靠性。
 

Pro-Dialog Plus Control

Pro-Dialog Plus combines intelligence with operating simplicity. The control constantly monitors all machine parameters and precisely manages the operation of compressors, expansion devices, fans and of the evaporator water pump for optimum energy efficiency.

 

User-friendly interface

-  The new backlighted LCD interface includes a manual control potentiometer to ensure legibility under any lighting conditions. The information is in clear text and can be displayed in English.

-  Unit uses intuitive tree-structure menus, similar to the Internet navigators. They are user-friendly and permit quick access to the principal operating parameters: number of compressors operating, suction/discharge pressure, compressor operating hours, set point, air temperature, entering/leaving water temperature.

 

 
                                                                                                                                                                                                                                                                                  

Advanced control function

-  Unit provides different control mode including LOCAL/REMOTE/CCN.

-  Remote control function including: Unit ON/OFF, dual set point control, demand limit control, user safety interlock, water pump control, operation indication, circuit alarm and alert etc.

-  Enable automatic reset of leaving water temperature according to return water temperature or outside air temperature to ensure optimum energy efficiency.

-  Control algorithm prevents excessive compressor cycling and permits reduction of the water quantity in the hydronic circuit (Carrier patent).

-  Automatic compressor unloading in case of abnormally high condensing pressure. If an abnomal incident occurs (e.g. fouled condenser coil, fan failure), Aquasnap continues to operate, but at reduced capacity.

控制功能先進

1. 30RB/RQ017~033提供室內機聯鎖控制與室內機通信控制兩種操作控制方式。

2. 30RB/RQ039~160提供本地(室內機聯鎖控制)和i-Vu

3. 自適應控制邏輯消除了壓縮機過頻迴圈的風險,始終使壓縮機按最佳的特性曲線運行

(適用多台室外機並聯運行時,自動平衡各機組的運行時間,並在一台機組發生故障時自動切換。

4. 節能模式可根據室外環境溫度和回水溫度自動重新設定冷水溫度以獲取最佳的能量利用效率。

Powerful Diagnostics

-  Unit can perform a quick test (manually or automatically) of all unit components and control points to verify the correct operation of unit

-  Real-time monitor all the controls and operation parameter, alarm when necessary.

-  Control system includes RS485 serial communication port for remote diagnosis or special diagnosis tools.

 診斷功能強    

快速檢測功能(手動)可確認各部件、各控制點是否正常。

運行中自動即時監控機組所有控制和安全參數,必要時報警,歷史報警記錄及報警重定。

控制系統中帶有RS485標準串列通訊介面,供遠距離或專用診斷工具分析,判斷時使用。

Sufficient safety measures

-  Password protection in case of mishandling.

-  Unit is protected against: compressor reverse, low chilled water temperature, high/low refrigerant pressure, excessive current, motor overload.

對於用戶設置/服務設置/工廠設置,提供密碼保護,防止誤操作。

具備完善的安全保護功能,如冷水溫度過低、製冷劑高低壓、排氣溫度過高、過電流保護、電機超載、水回路防凍保護、水泵超載、水流量過低等。

Group control

-  Master/slave control of two chillers operating in parallel with operating time equalization and automatic changeover in case of a unit fault.

-  Communication with other Building Management System (BMS) by selecting BacNet/J-Bus/LonTalk gateway.

標準通信協定上位機介面

提供RS485串列通信介面,可接入用戶樓宇自控系統,實現遠端開停、參數設置查詢等功能。

 

Performance data

 

30RB

 

30RB039S

30RB060S   30RB080S 30RB100S30RB120S

160S

Nominalcoolingcapacity*

kW

39.7

59.8                    80.5          100.9         118.0

157.9

Compressor power input

kW

13.0

20.4                     27.1           34.4          41.7

54.8

EER

kW/kW

2.88

2.84                     2.80           2.80          2.73

2.72

Operatingweight

 

 

 

 

Standard unit with hydronic module

 

 

 

 

Fixed speed single pump

kg

488

545                    562           877          912

1114

Fixed speed dual pump

kg

514

571                   588           922          960

1151

Unit without hydronic module

kg

458

515                   533           845          876

1075

Refrigerant

 

 

HFC-410A

 

Circuit A

kg

8.5

15.0                15.5           20.0          25.0

16.0

Circuit B

kg

-

-                -                -               -

16.0

Compressor

 

 

Hermetic scroll compressors, 48.3r/s

 

Circuit A

 

2

2                           2               3              3

2

Circuit B

 

-

-                          -                -               -

2

Number of capacity stages

 

2

2                          2               3              3

4

Minimum capacity

%

50

50                     50              33            33

25

Control

 

 

Pro-Dialog Plus

 

Condenser

 

 

Grooved copper tubes and aluminium fins

 

Fans

 

 

Axial Flying Bird IV with rotating shroud

 

Quantity

 

1

1                1               2              2

2

Total air flow

I/s

3800

3800          5300           7600          7600

10600

Speed

rpm

720

720            960           720          720

960

Evaporator

 

 

Brazed plate heat exchanger

 

Water volume

I

2.6

4.0              5.6             9.9           11.3

14.7

Nominal water flow rate

l/s

1.9

2.9              3.8             4.8            5.6

7.5

Unit internal water pressure drop

kPa

41

60              65              55            63

78

Max. water-side operating pressure without hydronic module

kPa

1000

1000          1000           1000          1000

1000

Hydronicmodule                                                                                      Pump, Victaulic screen filter, safety valve, expansion tank, purge valves etc. Water pump                                                                                                                                  Horizontal single-stage centrifugal pump

Water head external to chiller

 

Single pump at nominal water flow rate

kPa

227

194

196

223

201

181

Dual pump at nominal water flow rate

kPa

223

190

191

217

194

168

Expansion tank

I

12

12

12

35

35

35

Max. water-side operating pressure with hydronic module

kPa

400

400

400

400

400

400

Waterconnection                                                                                                                                     Victaulic

Diameter

 

DN50

DN50

DN50

DN65

DN65

DN65

Electricaldata

 

 

 

 

 

 

 

Main power supply                                                                                                                                 400V-3Ph-50Hz

Control power supply                                                                                                                     Via internal transformer

 

Nominal unit operating current draw

A

28

41

58

70

86

116

Maximum operating current draw

A

35

51

68

84

99

136

Maximum start-up current

A

115

146

212

199

243

280

Total fan power input

kW

0.8

0.7

1.6

1.5

1.5

3.2

Pump power input (single pump)

kW

1.3

1.3

1.8

2.1

2.3

4.7

Pump power input (dual pump)

kW

1.3

1.3

1.8

2.1

2.3

4.7

* Nominal cooling mode - evaporator entering/leaving water temperature 12/7°C, outside air temperature 35°C; Evaporator fouling factor - 0.018m2K/kW.